Plan Review Notes
Plan Review Notes For Permit 04010929
Permit Number 04010929
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-27 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE THE 2002 NEC FOR
 210.12 PLEASE SEE NOTE ON PLANS MENTION
 FOR RECEPTS ONLY. PLEASE ALSO SEE PLANS
 REFERENCE SD'S TO BE CIRCUITED TO BATH
 AND KITCHEN LT CIRCUIT. IF THIS IS THE
 CASE THEN BATH AND KITCHEN LTS WOULD BE
 REQUIRED TO BE ARC FAULT PROTECTED ALSO.
 PLEASE LIST CIRCUITS ON PANEL SCHEDULE.
  
 2)NOTE: PLEASE INCLUDE ARCH'S LICENSE #
 ON TITLE BLOCK AS REQ'D UNDER FS AND
 FAC 61G1-16.004
  
 3)NOTE: PLEASE SEE NOTE #3 ON PLANS.
 REFERENCES A CODE NO LONGER UNDER THE
 2002 NEC. # HAS COMPLETELY CHANGED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]