Plan Review Notes For Permit 04010929 |
Permit Number |
04010929 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-27 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE: PLEASE SEE THE 2002 NEC FOR | | 210.12 PLEASE SEE NOTE ON PLANS MENTION | | FOR RECEPTS ONLY. PLEASE ALSO SEE PLANS | | REFERENCE SD'S TO BE CIRCUITED TO BATH | | AND KITCHEN LT CIRCUIT. IF THIS IS THE | | CASE THEN BATH AND KITCHEN LTS WOULD BE | | REQUIRED TO BE ARC FAULT PROTECTED ALSO. | | PLEASE LIST CIRCUITS ON PANEL SCHEDULE. | | | | 2)NOTE: PLEASE INCLUDE ARCH'S LICENSE # | | ON TITLE BLOCK AS REQ'D UNDER FS AND | | FAC 61G1-16.004 | | | | 3)NOTE: PLEASE SEE NOTE #3 ON PLANS. | | REFERENCES A CODE NO LONGER UNDER THE | | 2002 NEC. # HAS COMPLETELY CHANGED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|