2004-10-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04010909 |
| ADD: 4847 FRED GLADSTONE DR |
| CONT: THE WHITING-TURNER CONT CO |
| TEL: (561)718-2367 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RD REVIEW |
| ACTION: DENIED |
| |
| 1) COMMENT# 1 FROM PREVIOUS REVIEW, |
| PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| THE SOILS REPORTS PROVIDED ARE NOT |
| SIGNED NOR SEALED. ORIGINAL SIGNATURES |
| REQUIRED, NOT STAMPED! |
| |
| 2)COMMENT#4 FROM THE PREVIOUS REVIEW |
| DELT WITH THE FL BUILDING CODE COMPON- |
| ENTS AND CLADDING REQUIRING PRODUCT TEST |
| ING REPORTS, MISSING REPORTS ARE THE |
| FOLLOWING: |
| A) WINDOWS FIXED AND SLIDERS, THE FL |
| APPROVAL SHEETS WERE SUBMITTED BUT THE |
| PRODUCT TESTING REPORTS AND TECHNICAL |
| DRAWINGS ARE MISSING. |
| B)SWING EXTERIOR DOORS-YKK AP AMERICA, |
| NON-IMPACT HIGHLIGHTED, NO REPORT NOR |
| TECHNICAL DRAWINGS.WILL REQUIRE SHUTTERS |
| C) ROOFING ASSEMBLIES- ALTUSA ROOF TILE |
| SUBMITTED REPORT METRO-DADE REPORT, BUT |
| THE FL APPROVAL IS FOR A SBCCI REPORT. |
| D) STORM SHUTTERS- NO INFORMATION WAS |
| SUBMITTED. |
| |
| BUILDING PLAN REVIEW |