2004-02-24 00:00:00 | DENIED |
| |
| 1)RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT A SIGNED AND SEALED COPY OF A |
| SOIL BORING TEST REPORT AS REQUIRED BY |
| FBC 1804.2.2. |
| |
| 3) FBC TABLE 1604.1 REQUIRES ATTICS WITH |
| STORAGE TO HAVE A 30 PSF LIVE LOAD AND |
| ATTICS WITHOUT STORAGE TO HAVE 10 PSF |
| LIVE LOAD. SPECIFY ON THE PLANS. |
| |
| 4) THE WINDOW SCHEDULE ON SHEET 3 |
| SPECIFIES A 3617 AWNING WINDOW AND THE |
| ELEVATION ON SHEET 1 SHOWS A 3020 |
| HORIZONTAL ROLLING WINDOW. PLEASE |
| CORRECT. |
| |
| 5) THE TRANSOM WINDOW ABOVE THE ENTRY |
| DOORS IS NOT LISTED IN THE WINDOW |
| SCHEDULE. |
| |
| 6) SPECIFY THE WINDLOAD PRESSURES FOR |
| THE EXTERIOR SWING DOORS AND THE TRANSOM |
| WINDOW ABOVE ENTRY DOORS. |
| |
| 7) THE TITLES FOR THE LEFT AND RIGHT |
| ELEVATIONS ON SHEET 1 ARE REVERSED. |
| PLEASE CORRECT. |
| |
| 8) SPECIFY THE LOCATION AND MATERIALS |
| FOR THE DRAFTSTOPPING OF THE FLOOR/ |
| CEILING ASSEMBLY INTO AREAS LESS THAN |
| 500 SQFT AS REQUIRED BY FBC 2305.2.2. |
| |
| 9) SUBMIT COMPLETED FORM FOR LOCAL |
| PRODUCT APPROVAL FOR THE COLLIER GARAGE |
| DOORS. SPECIFY THE QUALITY ASSURANCE |
| ENTITY ON THE FORM. SEE RULE 9B-72. |
| THE DRAWINGS SUBMITTED ARE LIMITED TO A |
| MINIMUM SIZE OF 10'X 6' AND DOES NOT |
| APPLY TO THE 8'X7' GARAGE DOOR ON THE |
| PLAN. SUBMIT ADDITIONAL INSTALLATION |
| DRAWINGS FOR THE SMALL DOOR. |
| |