2004-04-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/9/04:
  
 A) FBC 1606.1.7SHEET 8,WIND LOAD.
 THIS COMMENT HAS NOT BEEN ADDRESSED, FOR
 A SECOND TIME (SEE COMMENT C BELOW FOR
 STATE STATUTE FEE TO BE CHARGED IF THIS
 COMMENT IS NOT ADDRESS BEFORE THE NEXT
 REVIEW).FBC 104.2.1 STATES THAT THE
 CODE SHALL NOT BE CITED AS A WHOLE OR IN
 PART.LIGHT POLE NOTE 1 SHALL NOT
 SIMPLY CITE THE CODE, IT SHALL STATE THE
 BASIC WIND SPEED, WIND IMPORTANCE FACTOR
 AND WIND EXPOSURE CATEGORY.AMEND THE
 PLAN.
  
 B) 61G15-23.002(2)FL. ADMIN. CODE
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE ENGINEER SHALL PRINT HIS
 NAME AND LICENSE NUMBER ON EACH SHEET
 EVEN WHEN PRACTICING THROUGH AN
 ENGINEERING BUSINESS.
  
 C) NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN