2004-02-27 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| STRUCTURAL SUBMITTAL ON 2-20-04 FOR |
| LIGHTING POLE EMBEDMENT CALCULATIONS. |
| |
| A) THE SCOPE OF PERMIT# 04010651 WAS |
| REDUCED TO INCLUDE 'CONDUIT ONLY'.THIS |
| WAS AGREED WITH C.R. DUNN. TO ALLOW WORK |
| TO COMMENCE EVENTHOUGH THE SUBMITTED |
| LIGHTING POLE STRUCTURAL DETAILS WERE |
| NOT VALID.THOSE STRUCTURAL DETAILS |
| WERE OMITTED FROM THE PERMIT APPROVED |
| SET OF PLANS BY REMOVAL OF SHEET 8 OF 11 |
| PRIOR TO PERMITTING.THE CURRENT |
| SUBMITTAL OF EMBEDMENT DETAILS MUST BE |
| SUBMITTED AS A REVISION TO THIS PERMIT |
| (WITH APPROPRIATE FEE) OR AS A SEPARATE |
| PERMIT APPLICATION AND SHALL INCLUDE A |
| A PLAN, WITH SEAL ETC PER COMMENT (B) |
| BELOW, THAT PROVIDES ALL OF THE |
| INFORMATION REQUIRED TO ADDRESS COMMENT |
| #1 FROM THE 1/20/04 PLAN REVIEW (COPY |
| ATTACHED). |
| |
| B) 61G15-23.002(2)FL. ADMIN. CODE. |
| IT IS NOTED THAT THE EMBEDMENT |
| CALCULATION COVER SHEET INCLUDES THE |
| ENGINEER'S SIGNATURE, SEAL, LICENSE # |
| AND COMPANY ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION #.TO ADDRESS COMMENT #2 |
| FROM THE 1/20/04 PLAN REVIEW, THAT INFO |
| SHALL ALSO BE ON THE STRUCTURAL PLAN |
| REFERENCED IN COMMENT (A) ABOVE. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |