2004-03-13 00:00:00DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 1.RISER B IS MISSING 1 W/C AND 1 TUB.
 2.RISER C IS MISSING BAR SINK.
 3.PLEASE DELETE OLD RISER DIAGRAM FROM
 PLANS.
 PLUMBING PLAN REVIEW BY