2004-03-18 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STATE PRODUCT APPROVAL FOR THE |
| COLLIER GARAGE DOOR HAS A STATUS OF |
| VALIDATED. SUBMIT STATE PRODUCT APPROVAL |
| WITH APPROVED STATUS. |
| |
| 3) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| 8'X 7' GARAGE DOOR. THE DRAWING THAT WAS |
| SUBMITTED FOR THE COLLIER GARAGE DOOR IS |
| LIMITED TO A MINIMUM SIZE OF 10'X 6'. |
| |
| 4) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| 2-4 X 6-8 EXTERIOR SINGLE OUTSWING DOOR |
| AT THE LAUNDRY ROOM. |
| |
| 5) THE LOCAL PRODUCT APPROVAL SUBMITTED |
| FOR THE BUTT GLASS WINDOW IS INCOMPLETE. |
| SEE RULE 9B-72. SPECIFY METHOD 1 OR |
| METHOD 2 ON THE FORM. INDICATE THE |
| CATEGORY OF PRODUCT. LIST AN APPROVED |
| THIRD PARTY ASSURANCE ENTITY. LIST ALL |
| THE INFORMATION THAT IS REQUIRED FOR AN |
| EVALUATION REPORT FROM A FLORIDA |
| PROFESSIONAL ENGINEER AS LISTED FOR ITEM |
| #5 IN 9B-72.040. SPECIFY ANY LIMITATIONS |
| (SUCH AS IMPACT PROTECTION REQUIRED). |
| LIST THE REQUIREMENTS THAT THE PRODUCT |
| COMPLIES WITH INCLUDING CODE SECTION |
| NUMBERS AND REFERENCE STANDARDS, SUCH AS |
| FBC 1606, 1707, 2406.2 AND TAS 202. |
| SUBMIT TEST REPORTS, TECHNICAL DOCUMENTS |
| CALCULATIONS, ETC. UPON WHICH THE |
| RATIONAL ANALYSIS IS BASED. PROVIDE A |
| DETAILED REPORT INDICATING HOW THE |
| CONCLUSIONS WERE REACHED. INDICATE THE |
| PARAMETERS FOR WHICH THE REPORT IS |
| VALID, SUCH AS GLASS SIZES, ANGLES, ETC. |
| |
| 6) THE PRODUCT APPROVAL FOR THE STORM |
| PANELS LISTS SEVERAL TYPES OF ANCHORS |
| AND CONNECTION TYPES. SPECIFY THE |
| ANCHORS AND CONNECTION TYPE THAT WILL BE |
| USED ON THIS PROJECT BY CIRCLING OR |
| HIGHLITING THE APPROPRIATE ONES ON THE |
| PRODUCT APPROVAL. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |