Date |
Text |
2004-02-12 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 3)1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| REVISE TRUSS ANCHOR SCHEDULE USING |
| VALUES THAT DO NOT INCLUDE THE ONE- |
| THIRD INCREASE. TRUSS ANCHORS ARE |
| REQUIRED TO HAVE STATE OR LOCAL PRODUCT |
| APPROVAL. |
| |
| 4)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 5) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVAL IN ACCORDANCE WITH RULE 9B-72, |
| FOR THE BUTT GLASS WINDOW. SPECIFY THE |
| TYPE OF GE SILCONE TO BE USED. THE |
| HEIGHT DIMENSION ON THE PLAN IS NOT |
| CONSISTANT. |
| |
| 6) THE COLLIER GARAGE DOOR REQUIRES |
| STATE OR LOCAL PRODUCT APPROVAL IN |
| ACCORDANCE WITH RULE 9B-72, INCLUDING |
| QUALITY ASSURANCE. SUBMIT FORM FOR LOCAL |
| PRODUCT APPROVAL. THE SIZE LIMITATION IN |
| THE ENGINEERED DRAWINGS EXCLUDE THE |
| SMALLER GARAGE DOOR SHOWN ON THE PLANS. |
| |
| 7) SUBMIT THE APPROVED ENGINEERING AND |
| INSTALLATION INSTRUCTIONS FOR THE ENTRY |
| DOOR. |
| |
| 8) SPECIFY THE MOUNT TYPE AND ANCHORS |
| THAT WILL BE USED FOR THE STORM PANELS. |
| |
| 9) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVAL FOR THE TRUSS ANCHORS THAT ARE |
| SPECIFIED ON THE PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |