Plan Review Notes
Plan Review Notes For Permit 04010304
Permit Number 04010304
Review Stop B
Sequence Number 2
Notes
Date Text
2004-03-19 00:00:00SECOND CHECKLIST
  
 AS PREVIOUSLY NOTED, IMPACT FEES MUST BE
 PAID TO THE COUNTY BEFORE A PERMIT MAY
 BE ISSUED.
  
 THE 2001 FLORIDA BUILDING CODE WITH THE
 2003 REVISIONS IS CURRENTLY INVOKED IN
 THE STATE OF FLORIDA.
  
 WEST PALM BEACH IS IN THE 140 MPH WIND
 ZONE, HOWEVER THE HVHZ IS APPLICABLE
 ONLY TO BROWARD AND DADE COUNTIES.SEE
 FBC 202 DEFINITIONS.
  
 ALSO PLEASE NOTE AND ENSURE COMPLIANCE
 WITH THE MINIMAL DESIGN CRITERIA IN FBC
 1606.1.7.THE IMPORTANCE AND EXPOSURE
 FACTORS ARE STILL ABSENT FROM THE PLANS
 AND WIND PRESSURE ZONES 1,2&3,
 (COMPONENTS AND CLADDING) ARE NOT SHOWN.
  
 PLEASE REMOVE ANY OUTDATED OR
 SUPERFLUOUS PAGES FROM THE PLANS.