Plan Review Notes
Plan Review Notes For Permit 04010287
Permit Number 04010287
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-23 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES. BRING BACK STAMPED
 DRAINGS AND PAID RECEIPT.
 3-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LIVE FOR ATTIC WITH
 OR WITHOUT STORAGE. TABLE 1604.1 FBC.
 4-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 B)ENTRY DOORS ARE PENDING FBC APPROVAL
 AND NEED MATCHING DRAWINGS.
 C)SLIDING DOORS ARE PENDING FBC APPROVAL
 AND NEED ASSEMBLY WITH TRANSOM ABOVE.
 D)ARCHWINDOWS ARE PENDING FBC APPROVAL
 AND NEED MATCHING DRAWINGS. 2 COPIES.
 E)FIXED WINDOWS ARE PENDING FBC APPROVAL
 AND NEED MATCHING DRAWINGS.
 F)SINGLE HUNG WINDOWS ARE PENDING FBC
 APPROVAL
 G)WINDOW MULLIONS ARE PENDING FBC APPRO-
 VAL AND CLEARLY INDICATE MULLIONS AND
 COMPONENTS TO BE USED IN THIS PROJECT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 H)GARAGE DOORS COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL WITH DOORS THAT MEET
 THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
 I)NEED FLORIDA OR LOCAL PRODUCT APPROVAL
 FOR ALL STRUCTURAL CONNECTORS.
  
 5-STORM SHUTTERS: A)REVISE KEY PLAN TO
 MATCH FLOOR PLAN SUBMITTED.
 B)REVISE INSTALLATION SCHEDULE. SEE DWGS
 FOR LIMITATIONS ON PANEL MIN/MAX SPAN.
 C)CLEARLY INDICATE ON PLANS MOUNTING
 CONDITIONS & ANCHOR TYPE & SPACING TO
 BE USED ACCORDING TO DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (MASONRY OR CONCRETE).
 6-CLARIFY HOW IS 4"X8" PRECAST LINTEL
 AT ENTRY DOOR HOLD IN PLACE TO RESIST
 LATERAL LOADS IF THE VERTICAL REINFOR-
 CEMENT IS SHOWN GOING AROUND LINTEL ON
 DETAIL ON SHEET A5. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE SPECIFICATIONS FOR ROOF TILE
 FASTENING. SEE SEC. 1606.3 FBC 2001 &
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-A)REVISE DOOR STRUCTURAL BUCK DETAIL:
 HOW CAN A 1 1/2 TAPCON FASTEN A 2X
 BUCK. SEC. 104.2.1.2 CITY AMENDMENTS.
 B)REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION. ALSO, DETAIL TO SHOW
 REAL OPENING CONDITIONS. EG: THICKNESS
 OF WALL AS SHOWN ON DOOR BUCK DETAIL.
  
 9-SHEET A5: CONNECTOR TA15 SPECIFIED AT
 LANAI ROOF DOESN'T WORK. CONNECTOR IS
 DESIGNED TO GO AROUND TOP OF TRUSS
 CHORD. REVISE/CLARIFY AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-OWES $2.28 FOR UPDATED VALUATION.SEE
 ATTACHED RECEIPT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.