Notes |
Date |
Text |
2004-01-13 00:00:00 | | | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE NOTE, ALL PLANS DRAWN | | BY AN ARCHITECT/ENGINEER CONTAIN- | | -ING A TITLE BLOCK: MUST BE SIGNED, | | DATED AND SEALED BY THAT ARCH/ENG. | | PER FS 481.221 471.025 | | FAC 61G15-23.002, 61G1-16.004 | | INITIALS ARE NOT ACCEPTABLE PER FBPE. | | | | 2} THE BATH AND "EXT DOCK" LISTED ON THE | | PANEL SCHEDULE IS IN VIOLATION OF | | 210.11(C)(3),NO OTHER OUTLETS. | | | | 3} THE BATH NEEDS ANOTHER RECEPTACLE TO | | COMPLY WITH 210.52(D). | | | | 4} THE BEDROOM AND DINING ROOM REQUIRE | | SMOKE DETECTORS TO COMPLY WITH 905.2.2 | | FBC,AND CH.8 NFPA-72. | | | | 5} PLEASE SEE RECEPTS SERVING | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | SEC'S 1,2,3,4 AND 5 | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|