Plan Review Notes
Plan Review Notes For Permit 04010280
Permit Number 04010280
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALED BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
 INITIALS ARE NOT ACCEPTABLE PER FBPE.
  
 2} THE BATH AND "EXT DOCK" LISTED ON THE
 PANEL SCHEDULE IS IN VIOLATION OF
 210.11(C)(3),NO OTHER OUTLETS.
  
 3} THE BATH NEEDS ANOTHER RECEPTACLE TO
 COMPLY WITH 210.52(D).
  
 4} THE BEDROOM AND DINING ROOM REQUIRE
 SMOKE DETECTORS TO COMPLY WITH 905.2.2
 FBC,AND CH.8 NFPA-72.
  
 5} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]