2004-01-14 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ON THE PLANS FOR CODE COMPLIANCE.
  
 1} THE 1/0 FEEDER FROM THE METER TO THE
 PANEL IS NOT LARGE ENOUGH FOR 200
 AMPS.SEE 310.15(B)(6).
  
 2} THERE ARE 4 SMALL APPLIANCE CIRCUITS
 SHOWN IN THE LOAD CALCS (6000/1500=4)
 BUT ONLY 3 IN THE PANEL SCHEDULE,PLEASE
 CORRELATE.
  
 3} THE DINING ROOM & MORNING
 (BREAKFAST)ROOM WIRE SIZE LISTED ON THE
 SCHEDULE
 MUST BE # 12 PER210.52(B)(1),SMALL APP.
  
 4}THE RANGE CALCULATION MUST COMPLY WITH
 220.19.8KW MIN.
  
 5} THE OCP @60 AMPS IS TOO LARGE FOR THE
 #8 WIRE FOR THE RANGE LISTED ON THE
 PANEL SCHEDULE PER310.16.
  
 6} THE GARAGE RECEPTACLES DO NOT COMPLY
 WITH 210.8(A)(2),GFI.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]