Notes
Date Text
2004-04-12 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE E-500, NOTE MENTIONS
 TO SEE E-500 FOR PANEL SCHEDULES, BUT
 NONE SHOWN.
  
 2)NOTE; WIND LOADS FOR LIGHTING/POLE
 IS REQ'D TO BE PER FBC 140 MPH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  