Plan Review Notes
Plan Review Notes For Permit 04010207
Permit Number 04010207
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
 SIGNATURE MUST BE ORIGINAL ALONG WITH
 DATE.
  
 2 )NOTE: PLEASE INCLUDE ALL LICENSE
 #'S ON THE REQ'D TITLE BLOCK.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION #'S WHERE REQ'D.
 ARCH'S/ENGINEERS.
 PER FS 471.023, FAC 61G15-23.002 (ENG'S)
 PER FS 481.219, FAC 61G1-16.004 (ARCH'S)
  
 3)NOTE: PLEASE SEE FIRE REVIEW NOTES,
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 5)NOTE: PLEASE CLARIFY IF PANELS ARE
 NEW OR EXSITING? SHOWN AS NEW. IF NEW
 PLEASE SHOW INFORMATIONWHERE AND HOW
 THESE PANELS ARE BEING FED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]