2004-01-12 00:00:00 | ************ UNSAT ************** |
| |
| 1)NOTE: PLEASE NOTE, ALL PLANS DRAWN |
| BY AN ARCHITECT/ENGINEER CONTAIN- |
| -ING A TITLE BLOCK: MUST BE SIGNED, |
| DATED AND SEALD BY THAT ARCH/ENG. |
| PER FS 481.221 471.025 |
| FAC 61G15-23.002, 61G1-16.004 |
| SIGNATURE MUST BE ORIGINAL ALONG WITH |
| DATE. |
| |
| 2 )NOTE: PLEASE INCLUDE ALL LICENSE |
| #'S ON THE REQ'D TITLE BLOCK. |
| PLEASE ALSO INCLUDE CERTIFICATE OF |
| AUTHORIZATION #'S WHERE REQ'D. |
| ARCH'S/ENGINEERS. |
| PER FS 471.023, FAC 61G15-23.002 (ENG'S) |
| PER FS 481.219, FAC 61G1-16.004 (ARCH'S) |
| |
| 3)NOTE: PLEASE SEE FIRE REVIEW NOTES, |
| PLEASE SEE 700.12E FOR CIRCUITING OF |
| EM/EXT LTS. |
| |
| 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 5)NOTE: PLEASE CLARIFY IF PANELS ARE |
| NEW OR EXSITING? SHOWN AS NEW. IF NEW |
| PLEASE SHOW INFORMATIONWHERE AND HOW |
| THESE PANELS ARE BEING FED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |