2004-02-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010207
 ADD: 1475 CENTREPARK # 301
 CONT: LEIGHTON & MCGINN
 TEL: (561)722-9696
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SIGNATURES ARE TO BE ORIGINALS SEE "E"
 PAGES, COPIED.
  
 2) 905.1.5, PLEASE PROVIDE INFORMATION
 FOR EMERGENCY LIGHTING AND ALARMS.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) TENANT SEPERATION WALL, "M" PAGES
 INDICATE MEDIUM PRESSURE DUCT THROUGH
 TENANT SEPERATION WALLS? RATING? FIRE-
 DAPPERS!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026