Plan Review Notes
Plan Review Notes For Permit 04010183
Permit Number 04010183
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-09 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 A RISER DIAGRAM MUST BE SUBMITTED FOR
 REVIEW PER 215.5. PLEASE SUBMIT SAME AS
 A REVISION TO THIS PERMT OR A NEW
 PERMIT MAY BE APPLIED FOR AS A SERVICE
 CHANGE.
 THERE IS NO RECORD OF A PERMIT BEING
 ISSUED FOR THE "EXISTING" 200 AMP PANEL
 THAT IS REFERRED TO ON THE LOAD
 CALCULATION,PLEASE INCLUDE THAT WHEN
 APPLYING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  