Plan Review Notes
Plan Review Notes For Permit 04010144
Permit Number 04010144
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR DOORS, WINDOWS,
 GLASS BLOCK, ROOF TILE, MULLIONS AND
 ALL STRUCTURAL CONNECTORS UNDER A
 SEPARATE PERMIT.
 2-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. REVISE AS REQUIRED
 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE.
 4-TYPICAL WALL SECTION A/4: SPECIFY
 WHERE ARE TABLES 6 AND 8 FOR ROOF TILE
 FASTENING TAKEN FROM?. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-SHEET #7: A)REVISE/CLARIFY DESIGN
 PRESSURES SHOWN ON REAR ELEVATION.
 THEY DON'T MATCH THOSE SHOWN ON DWG 3B
 B)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH THOSE SHOWN ON WINDOW SCHEDULE.
 C)REVISE FLOOR PLAN & ROOF FRAMING PLAN
 NOTES TO REFLECT CHANGE OF WOOD BM TO
 CONCRETE BEAM. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 6-SHEET #3:CLARIFY/REVISE NOTE REGARDING
 CONNECTORS SELECTED FOR UPLIFT.