Plan Review Notes For Permit 04010144 |
Permit Number |
04010144 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | PRODUCT APPROVAL FOR DOORS, WINDOWS, | | GLASS BLOCK, ROOF TILE, MULLIONS AND | | ALL STRUCTURAL CONNECTORS UNDER A | | SEPARATE PERMIT. | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | DWG #2 DON'T MATCH. REVISE AS REQUIRED | | 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. | | 4-TYPICAL WALL SECTION A/4: SPECIFY | | WHERE ARE TABLES 6 AND 8 FOR ROOF TILE | | FASTENING TAKEN FROM?. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 5-SHEET #7: A)REVISE/CLARIFY DESIGN | | PRESSURES SHOWN ON REAR ELEVATION. | | THEY DON'T MATCH THOSE SHOWN ON DWG 3B | | B)WINDOWS SHOWN ON REAR ELEVATION DON'T | | MATCH THOSE SHOWN ON WINDOW SCHEDULE. | | C)REVISE FLOOR PLAN & ROOF FRAMING PLAN | | NOTES TO REFLECT CHANGE OF WOOD BM TO | | CONCRETE BEAM. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 6-SHEET #3:CLARIFY/REVISE NOTE REGARDING | | CONNECTORS SELECTED FOR UPLIFT. |
|