Plan Review Notes
Plan Review Notes For Permit 04010105
Permit Number 04010105
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-16 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH CHAPTER 481
 FLORIDA STATUTES WHEN SUBMITTING PLANS
 FOR PUBLIC RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS/WINDOWS
 TYPE, MULLIONS, GLASS BLOCK ROOF TILE,
 STRUCTURAL CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO MATCH IT. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATC. CHECK SIZE OF FASTENER.
 6-UPDATE TRUSS ANCHOR SCHEDULE. SEE SEC.
 1609.4.3 FBC 2001.
 B)SPECIFY SIZE OF USP RT STRAP. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE. SEC. 104.2.1.1 CITY AMENDMENTS.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-REVISE DESIGN PRESSURES. SEE TABLES
 1606.2B AND 1606.2E FOR SIZE AND
 LOCATION. PROVIDE CALCULATIONS FOR
 DIFFERENT DESIGN PRESSURES. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG-7 CONNECTOR. FASTENER SPECIFIED IS
 DIFFERENT FROM THAT PUBLISHED ON
 CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.