Plan Review Notes
Plan Review Notes For Permit 04010083
Permit Number 04010083
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ALL DRAWINGS TO HAVE ALL ARCHITECT'S
 INFORMATION AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES.
 2-PROVIDE COMPLETE CURRENT PRODUCT
 APPROVALS FOR ALL DOORS, WINDOWS,
 MULLIONS, GLASS BLOCK, ROOF TILE AND
 ALL STRUCTURAL CONNECTORS UNDER A
 SEPARATE PERMIT.
 3-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. REVISE AS REQ'D.
 4-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001.
 5-DWG #2: A)REVISE/CLARIFY TRUSS ANCHOR
 SCHEDULE.
 B)PROVIDE HOLD DOWN DETAILS AND CALCS
 AS SPECIFIED ON NOTE ON THIS DWG.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-SPECIFY ROOF TILE FASTENERS. SEE SEC.
 1606.3 FBC 2001 AND SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE REVISED ROOF FRAMING PLAN
 SHOWING CHANGE OF BEAM AT REAR PORCH.
 WOOD TO MASONRY.
 8-SHEET #3:CLARIFY NOTE REGARDING UPLIFT
 CALCS AND CONNECTORS SELECTED.