Plan Review Notes For Permit 04010071 |
Permit Number |
04010071 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE CURRENT PRODUCT APPRO | | VAL FOOR ALL DOORS, WINDOWS, MULLIONS, | | ROOF TILE, GLASS BLOCK AND ALL | | STRUCTURAL CONNECTORS UNDER A SEPARATE | | PERMIT AS REQ'D BY BUILDING OFFICIAL. | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | DWG #2 DON'T MATCH. REVISE AS REUIRED. | | 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. | | 4-TYPICAL WALL SECTION A/4: CLARIFY | | WHERE ARE TABLES 6 AND 8 REFERING TO | | ROOF FASTENERS TAKEN FROM?. SECTION | | 1606.3 FBC 2001 AND SEC. 104.2.1.1 | | CITY AMENDMENTS TO FBC 2001. | | 5-SHEET #7: A)REVISE/CLARIFY DESIGN | | PRESSURES SHOWN ON ELEVATION. | | B)REVISE ALL NOTES ON FLOOR PLAN & ROOF | | FRAMING PLAN TO REFLECT CHANGE OF BEAM | | | | 6-SHEET #3: CLARIFY NOTE REGARDING THE | | UPLIFT CALCS AND CONNECTORS SELECTED. |
|