Plan Review Notes For Permit 04010064 |
Permit Number |
04010064 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-09 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE CURRENT PRODUCT APPRO | | VAL FOR ALL DOORS, WINDOWS, MULLIONS, | | GLASS BLOCK, ROOF TILE AND ALL | | STRUCTURAL CONNECTORS UNDER A SEPARATE | | PERMIT AS REQ'D BY BUILDING OFFICIAL. | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | DWG #2 DON'T MATCH. REVISE AS REQUIRED | | 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. | | 4-TYPICAL WALL SECTION DETAIL A/4: | | CLARIFY WHERE ARE TABLES 6 & 8 TAKEN | | FROM? SEE SEC. 1606.3 FBC 2001 & SEC. | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | 5-SHEET #7: A)REVISE/CLARIFY DESING PRE- | | SSURES ON EXTERIOR ELEVATION OPENINGS. | | B)WINDOWS SHOWN ON ELEVATION DON'T MATCH | | WINDOW SCHEDULE. | | C)REVISE ALL NOTES ON FLOOR PLAN & ROOF | | PLAN TO REFLECT CHANGE OF BEAM. | | | | 6-SHEET #3: CLARIFY NOTE REGARDING THE | | UPLIFT CALCS AND CONNECTORS SELECTED. |
|