Plan Review Notes For Permit 04010058 |
Permit Number |
04010058 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-09 00:00:00 | ************** UNSAT ************* | | | | 1)NOTE: PLEASE BE SURE PLANS ARE SEALED | | W/ RAISED/EMBOSSED SEAL IS CLEAR AND | | VISABLE. | | | | 2)NOTE: PLEASE CLARIFY CIRCUITING FOR | | LIGHTING . PLEASE ALSO SEE 700.12E FOR | | EM/EXT LTS. | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125% PER 215.3,230.42 ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|