2004-02-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO PROVIDE ALL HIS INFO IN
 ALL DWGS AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTES.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR DOORS, WINDOWS,
 MULLIONS, GLASS BLOCK, ROOF TILE AND
 ALL STRUCTURAL CONNECTORS UNDER A
 SEPARATE PERMIT.
 3-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. REVISE AS REQ'D.
 4-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001.
 5-DWG #2: A)REVISE/CLARIFY TRUSS ANCHOR
 SCHEDULE.
 B)PROVIDE ENGINEER'S DETAILS AND CALCS
 AS SPECIFIED ON NOTE.
  
 6-SPECIFY ROOF TILE FASTENERS. SECTION
 1606.3 FBC 2001 & SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 7-PROVIDE REVISED ROOF FRAMING PLAN
 SHOWING CONCRETE BEAM INSTEAD OF WOOD
 BEAM. SEC. 104..2.1.2 CITY AMENDMENTS.
 8-SHEET #3: CLARIFY NOTE REGARDING
 UPLIFT AND CONNECTORS SELECTED.