2004-03-18 00:00:00PROVISO:
 PER THE REVISION TO THE 2001 FBC(M)601.4
 EFFECTIVE JUNE 30, 2003:
  
 WHEN CALCULATING RETURN AIR FROM THE
 MASTER BEDROOM ALL SUPPLY AIR INTO THE
 SUITE IS TO BE INCLUDED FOR THE TOTAL OF
 SUPPLY AIR.
 I.E., 10" SUPPLY TO BEDROOM = 78 SQ IN
 4""MASTER CLOSET = 13 SQ IN
 4""MASTER BATHRM = 13 SQ IN
 TOTAL = 104 SQ IN X 1.5 = 156 SQ IN =
 15" RETURN AIR JUMPER.
  
 PLEASE REVISE RETURN AIR FOR THE MASTER
 BEDROOM TO REFLECT THE REQUIRED SIZE FOR
 A RETURN AIR JUMPER.
  