Plan Review Notes For Permit 03121642 |
Permit Number |
03121642 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-06-11 00:00:00 | 1) LOCKING CAPS ARE TO BE INSTALLED | | ON FDC. | | | | 2) THE TWO BURNER DEVICE IN ROOMS IS | | A STOVE OR HOT PLATE ARRANGEMENT. | | PLEASE ADVISE. | | | | 3) TACTILE SIGNAGE SHOULD BE LOCATED | | AT STAIR OPENINGS NOT INSIDE THE | | STAIRS. | | | | 4) LOW WALL DETAIL SHALL RESIST | | HORIZONTAL AND VERTICAL LOADS EXPECTED | | TO BE PLACED UPON IT. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|