Date |
Text |
2004-04-29 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| A) FROM PREVIOUS REVIEW: COMMENT NUMBER |
| SHALL REMAIN THE SAME TO AVOID CONFUSION |
| 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2 |
| ACCESSIBLE UNITS, SLEEPING ROOMS, AND |
| SUITES. - RESPONSE NOTED, BUT THE SHOWER |
| SHOWN IN THESE THREE UNITS ARE NOT ROLL- |
| IN SHOWERS. SEE ATTACHED SHEET, FIG. 57, |
| SHOWING EXAMPLE OF ROLL-IN SHOWER. |
| 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4 |
| CLASSED OF SLEEPING ACCOMMODATIONS. RE- |
| SPONSE NOTED, PLEASE INDICATE TYPES OF |
| SLEEPING ACCOMMODATION AVAILABLE TO CON- |
| FIRM THAT ALL CLASSES ARE REPRESENTED. |
| 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC- |
| TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY |
| C/O'S MAY BE USED. 708.3.5 - RESPONSE |
| NOTED, BUT CLEANOUTS ARE NOT SHOWN. ALSO |
| SHOW CLEANOUTS MENTIONED ABOVE ON BLDG |
| DRAIN ISOMETRIC SHEET P-8. |
| 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. KITCHEN SINK SHALL DISCHARGE |
| DOWN-STREAM OF THE WET VENT. 909.1 - |
| RESPONSE NOTED - PLEASE HAVE CHANGES |
| REFLECTED ON THE SANITARY RISER DIAGRAM |
| ALSO. |
| 18- F. DELIVERY PRESSURE NOT INDICATED |
| ON PLANS. INDICATE THE DELIVERY PRESSURE |
| (PSI) PER FBC-2001 FUEL GAS CODE SECTION |
| 402.2. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |