Plan Review Notes
Plan Review Notes For Permit 03121642
Permit Number 03121642
Review Stop P
Sequence Number 2
Notes
Date Text
2004-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW: COMMENT NUMBER
 SHALL REMAIN THE SAME TO AVOID CONFUSION
 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2
 ACCESSIBLE UNITS, SLEEPING ROOMS, AND
 SUITES. - RESPONSE NOTED, BUT THE SHOWER
 SHOWN IN THESE THREE UNITS ARE NOT ROLL-
 IN SHOWERS. SEE ATTACHED SHEET, FIG. 57,
 SHOWING EXAMPLE OF ROLL-IN SHOWER.
 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4
 CLASSED OF SLEEPING ACCOMMODATIONS. RE-
 SPONSE NOTED, PLEASE INDICATE TYPES OF
 SLEEPING ACCOMMODATION AVAILABLE TO CON-
 FIRM THAT ALL CLASSES ARE REPRESENTED.
 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC-
 TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY
 C/O'S MAY BE USED. 708.3.5 - RESPONSE
 NOTED, BUT CLEANOUTS ARE NOT SHOWN. ALSO
 SHOW CLEANOUTS MENTIONED ABOVE ON BLDG
 DRAIN ISOMETRIC SHEET P-8.
 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. KITCHEN SINK SHALL DISCHARGE
 DOWN-STREAM OF THE WET VENT. 909.1 -
 RESPONSE NOTED - PLEASE HAVE CHANGES
 REFLECTED ON THE SANITARY RISER DIAGRAM
 ALSO.
 18- F. DELIVERY PRESSURE NOT INDICATED
 ON PLANS. INDICATE THE DELIVERY PRESSURE
 (PSI) PER FBC-2001 FUEL GAS CODE SECTION
 402.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]