Plan Review Notes For Permit 03121642 |
Permit Number |
03121642 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-04-24 00:00:00 | DENIED: | | RESPONSE #2 | | DRYER DUCT TO PENETRATE AT PLENUM BOX | | CEILING DIFFUSER.PLEASE INDICATE THE | | HEIGHT OF THE CEILING DIFFUSER.PER | | 2001 FBC(M) 504.4, EXHAUST TERMINATION | | SHALL BE NON-SCREENED WITH A BACKDRAFT | | DAMPER.PLEASE PROVIDE DETAIL OF DRYER | | TERMINATION.PROVIDE ADDITIONAL | | INFORMATION ON THE DRYER; (A) COMMERCIAL | | OR RESIDENTAL (B) DOES IT EXHAUST MORE | | THAN 200 CFM (C) DEVELOPED LENGTH | | EXCEEDS 25 FT. | | | | PROVISO: | | PLEASE NOTE, THE DIRECTIONAL BEARING ON | | THE A/C PLANS CONFLICT WITH THE | | ARCHITECTURAL PLANS. | | | | PLAN SHEET AC-4 POOL EQUIPMENT ROOM, | | 10 FT SEPARATION REQUIRED BETWEEN THE | | EXHAUST & INTAKE LOUVER. | | | | PLEASE NOTE, PLANS INDICATE EXHAUST & | | FRESH AIR INTAKE TEMINATING IN THE | | CEILING OF THE VEHICULAR DRIVE THRU. | | EXHAUST SHALL TERMINATE AS TO NOT CREATE | | A NUISANCE (2001 FBC(M) 401.5.2).FRESH | | AIR INTAKES SHALL BE LOCATED AS TO NOT | | RECIRCULATE NOXIOUS CONTAMINANTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|