Plan Review Notes
Plan Review Notes For Permit 03121642
Permit Number 03121642
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-04-23 00:00:001) TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 2) ALL SHAFTWAYS LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE IDENTIFIED
 BY SIGNAGE "SHAFTWAY".
  
 3) KNOX-BOX LOCKING CAPS REQUIRED
 ON FIRE DEPARTMENT CONNECTION.
  
 4) PANIC HARDWARE REQUIRED ON EXIT
 DOORS LOCATED FOR THE POOL DECK.
  
 5) WHAT PREVENTS PERSONS FROM LEAVING
 THE EXTERIOR DOOR NEAR SUITE 105 AND
 GOING DIRECTLY INTO THE VEHICULAR EXIT
 DRIVE LANE.
  
 6) ARE THE STAIRS ON THE ROOF TERRACE
 SLIP RESISTANT?
  
 7) THE BUILDING ADDRESS IS NOTED ON
 THE FRONT ELEVATION. WILL THE LOCATION
 BE CLEARLY VISIBLE AT ITS MOUNTING
 HEIGHT. PLEASE ADVISE.
  
 8) SIGNS REQUIRED IN STAIRWELLS
 INDICATING STAIR IDENTITY, TERMINUS
 LOCATIONS AT TOP AND BOTTOM, ETC.
  
 9) ALL FIRE RATED DOORS SHALL BE
 EQUIPED WITH SELF-CLOSING DEVICES
 TO CAUSE THE DOORS TO POSITIVELY LATCH.
  
 10) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM AND
 FIRE SPRINKLER SYSTEM.
  
 11) WHAT PREVENTS VEHICULAR DAMAGE
 TO THE FIRE-LINE BACKFLOW DEVICE.
  
 12) THE MINIMUM SIZE FIRE LINE SHALL
 BE AT LEAST 6 INCHES. ON SHEET FP1
 THREE INCH LINES ARE SHOWN. PLEASE
 ADVISE.
  
 13) THE REQUIRED FIRE ALARM SYSTEM SHALL
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 14) THE FIRE ALARM SYSTEM CIRCUITS
 SHALL BE CLASS A, STYLE D OR FULLY
 ADDRESSABLE.
  
 15) NO ELECTRICAL ALLOWED IN STAIRWELL
 EXCEPT REQUIRED EMERGENCY LIGHTING
 EQUIPMENT FOR THE STAIRWELLS.
  
 16) THE FIRE PUMP ROOM IS REQUIRED
 TO HAVE EMERGENCY LIGHTING.
  
 17) REQUIRED SMOKE DETECTORS APPEAR
 TO BE MISSING FROM SEVERAL UNITS
 LOCATED ON THE SECOND FLOOR. SOME
 UNITS HAVE SMOKE DETECTORS IN THE
 HALLWAY AND SOME DO NOT. PLEASE
 EXPLAIN RATIONALE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910