2004-04-27 00:00:00*** UNSAT ***
  
 PLEASE SEE SOME COMMENTS FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE IT APPEARS NOW USEAGE
 HAS NOW BEEN CLARIFIED FOR HOTEL USEAGE.
 PLEASE SEE 240.24B FOR LOCATIONS OF
 PANELS.
  
 2)NOTE: PLEASE SEE NOTE;5 FROM FIRST
 REVIEW. PLEASE PROVIDE NOTE/INFORMATION
 IN REFERENCE TO LIGHTING FOR NIGHT TIME
 SWIMMING? PLEASE PROVIDE AS FOR WIND
 LOAD ON LT POLE PER FBC 140 MPH.
  
 3)NOTE: PLEASE SEE TWO PANEL HC'S SHOWN
 ON RISER.
  
 4)NOTE: PLEASE SEE NOTE: 13 FROM FIRST
 REVIEW. PLEASE PROVIDE ALL INFORMATION
 FOR FIRE PUMP AND ASSOC EQUIPMENT.
 695.4B1, 230.76,230.79,110.27
 PLEASE NOTE: LOCATION OF DISC MEANS FOR
 FIRE PUMP, 695.3, 230.72.
 LOCATION OF MAINS PER NEC AND FIRE DEPT
 SHUTTING DOWN OF FIRE PUMP.
 KNOW BOX ETC. LOCATION ON SECOND FLR
 HAS NOT BEEN APPROVED BY THIS OFFICE AT
 THIS TIME.
 PLEASE SUBMIT SPECS FOR ALL EQUIPMENT.
  
 5)NOTE: RESPONSE TO NOTE:9 FROM FIRST
 REVIEW MENTIONS GRC FOR ALL CONDUIT
 INSTALLATIONS / FEEDERS ETC. PLEASE
 VERIFY THIS. THIS IS ONLY A NOTE.
  
 PLEASE SEE FS 553.80(2)(B) FOR ANY
 COMMENTS BEING REPEATED FOR THE SAME
 COMMENTS. THIS NOTICE IS GIVEN ON
 SECOND REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  