2004-01-31 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| |
| 1) SHT C-6 GREASE/WATER INTECEPTOR SHALL |
| BE SIZED BY RODNEY COMPO, ENVIRONMENTAL |
| COMPLIANCE MGR. PER WASTE ORD. #2938. |
| PLEASE CONTACT MR. COMPO AT (561) 837- |
| 4074. |
| 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2 |
| ACCESSIBLE UNITS, SLEEPING ROOMS, AND |
| SUITES. |
| 3) SHOW COMPLIANCE WITH SECTION 11-9.1.3 |
| SLEEPING ACCOMMODATIONS FOR PERSONS WITH |
| HEARING IMPAIRMENTS. |
| 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4 |
| CLASSES OF SLEEPING ACCOMMODATIONS. |
| 5) SHOW COMPLIANCE WITH SECTION 11-9.2.3 |
| HOTEL, MOTEL AND CONDOMINIUM SPECIAL |
| ACCESSIBILITY FEATURE. |
| 6) SHT P-1 MEN'S AND WOMEN'S RESTROOMS |
| #'S 148 & 135, FLOOR DRAINS ARE NOT VEN- |
| TED. CORRECT ON THE FLOOR PLAN AND SANT. |
| RISER DIAGRAM. 901.2.1 |
| 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC- |
| TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY |
| C/O'S MAY BE USED. 708.3.5 |
| 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. KITCHEN SINK SHALL DISCHARGE |
| DOWN-STREAM OF THE WET VENT. 909.1 |
| 9) SHT P-1 IDENTIFY SANITARY LINE AND |
| STACK LOCATED IN WALL BETWEEN BDRM 130 |
| AND CORRIDOR. IDENTIFY STACK. |
| 10) SHT P-1 GAS PIPE DROPING DOWN FROM |
| SHT P-2 BY STAIRWAY #1 NOT SHOWN ON P-1 |
| SHEET. PLEASE CLAIRFY. 104.2.1 |
| 11) SHT P-6 TABLE 906.1 MAXIMUM DISTANCE |
| FROM TRAP TO VENT IS 10 FEET. FLOOR |
| DRAIN IN MECH. ROOM BACK TO VENT SEEMS |
| TO EXCEED THIS DISTANCE. |
| 12) SHT P-7 SANT. RISER S/8 SHOWS FLOOR |
| SINKS ON 2ND, 3RD, 4TH, & 5TH FLOORS. |
| SHT P-2 SHOWS S/8 UP TO MEZZ. FLOOR AT |
| COL. LINE "D" BETWEEN LAUNDRY & ELECTRIC |
| ROOM BUT NOT SHOWN ABOVE ON SHTS P-3, P- |
| 4, OR P-5, NOR DOES IT SHOW FLOOR SINKS |
| ON ANY OF THESE FLOORS. SHT P-8 SHOWS |
| S/8 PICKING UP A WASH MACHINE AND THEN |
| VENTING THRU THE ROOF. PLEASE CLAIRFY. |
| 104.2.1 |
| 13) A FLOOR DRAIN IS REQUIRED IN THE |
| LAUNDRY PER SECTION 412.4. |
| 14) SHT P-7 WATER ISOMETRICS ALL UNITS. |
| AIR CHAMBERS ARE NOT APPROVED. DELETE |
| FROM RISERS. 604.9 - WATER HAMMER ARREST |
| ORS ARE REQUIRED AT THE WASH MACHINES, |
| DISHWASHERS, AND ICE MAKERS, AND SHALL |
| BE LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING PER |
| PDI-WH 201 AND MANUF. INSTALLATION IN- |
| STRUCTIONS. |
| 15) SHT P-9 WATER PIPING DRISTRIBUTION |
| ISOMETRIC, ICE MACHINE RISER. WATER |
| HAMMER ARRESTORS ARE REQUIRED AT EACH |
| WASH MACHINE PER 604.9. WATER HAMMER |
| ARRESTORS SHALL BE LOCATED NEAR THE FIX- |
| TURE IN AN "EFFECTIVE RANGE" NOT IN THE |
| CEILING. PDI-WH 201 AND MANUF. INSTALL. |
| INSTRUCTIONS. |
| 16) P-10 STORM WATER RISER DIAGRAM, THE |
| HORIZONTAL PIPE SIZE IS NOT CORRECT |
| WHERE 4"SD (2060 SF) & 4"SD (2160 SF) |
| MAXIMUM 1600 SF FOR 4" PIPE @ 1/8" PER |
| FOOT. SIZE ALL HORIZONTAL PIPE SECTIONS. |
| 17) SHT P-12 ALL PUMPS SHALL BE LISTED |
| BY AN APPROVED TESTING AGENCY. SUBMIT |
| MANUF. SPECS SHEETS. 303.4 |
| 18) SEPARATE GAS PERMIT REQUIRED. THE |
| FOLLOWING INFORMATION REQUIRED: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| SHOW VENTING IF DIRECT VENT. |
| H. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| I. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| REVIEW BY KEN STEVENS |