Plan Review Notes
Plan Review Notes For Permit 03121642
Permit Number 03121642
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1) SHT C-6 GREASE/WATER INTECEPTOR SHALL
 BE SIZED BY RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE MGR. PER WASTE ORD. #2938.
 PLEASE CONTACT MR. COMPO AT (561) 837-
 4074.
 2) SHOW COMPLIANCE WITH SECTION 11-9.1.2
 ACCESSIBLE UNITS, SLEEPING ROOMS, AND
 SUITES.
 3) SHOW COMPLIANCE WITH SECTION 11-9.1.3
 SLEEPING ACCOMMODATIONS FOR PERSONS WITH
 HEARING IMPAIRMENTS.
 4) SHOW COMPLIANCE WITH SECTION 11-9.1.4
 CLASSES OF SLEEPING ACCOMMODATIONS.
 5) SHOW COMPLIANCE WITH SECTION 11-9.2.3
 HOTEL, MOTEL AND CONDOMINIUM SPECIAL
 ACCESSIBILITY FEATURE.
 6) SHT P-1 MEN'S AND WOMEN'S RESTROOMS
 #'S 148 & 135, FLOOR DRAINS ARE NOT VEN-
 TED. CORRECT ON THE FLOOR PLAN AND SANT.
 RISER DIAGRAM. 901.2.1
 7) SHT P-1 CLEANOUTS REQUIRED NEAR JUNC-
 TION OF BLDG DRAIN AND BLDG SEWER. 2-WAY
 C/O'S MAY BE USED. 708.3.5
 8) SHT P-1 ALL UNITS, ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. KITCHEN SINK SHALL DISCHARGE
 DOWN-STREAM OF THE WET VENT. 909.1
 9) SHT P-1 IDENTIFY SANITARY LINE AND
 STACK LOCATED IN WALL BETWEEN BDRM 130
 AND CORRIDOR. IDENTIFY STACK.
 10) SHT P-1 GAS PIPE DROPING DOWN FROM
 SHT P-2 BY STAIRWAY #1 NOT SHOWN ON P-1
 SHEET. PLEASE CLAIRFY. 104.2.1
 11) SHT P-6 TABLE 906.1 MAXIMUM DISTANCE
 FROM TRAP TO VENT IS 10 FEET. FLOOR
 DRAIN IN MECH. ROOM BACK TO VENT SEEMS
 TO EXCEED THIS DISTANCE.
 12) SHT P-7 SANT. RISER S/8 SHOWS FLOOR
 SINKS ON 2ND, 3RD, 4TH, & 5TH FLOORS.
 SHT P-2 SHOWS S/8 UP TO MEZZ. FLOOR AT
 COL. LINE "D" BETWEEN LAUNDRY & ELECTRIC
 ROOM BUT NOT SHOWN ABOVE ON SHTS P-3, P-
 4, OR P-5, NOR DOES IT SHOW FLOOR SINKS
 ON ANY OF THESE FLOORS. SHT P-8 SHOWS
 S/8 PICKING UP A WASH MACHINE AND THEN
 VENTING THRU THE ROOF. PLEASE CLAIRFY.
 104.2.1
 13) A FLOOR DRAIN IS REQUIRED IN THE
 LAUNDRY PER SECTION 412.4.
 14) SHT P-7 WATER ISOMETRICS ALL UNITS.
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM RISERS. 604.9 - WATER HAMMER ARREST
 ORS ARE REQUIRED AT THE WASH MACHINES,
 DISHWASHERS, AND ICE MAKERS, AND SHALL
 BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING PER
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
 15) SHT P-9 WATER PIPING DRISTRIBUTION
 ISOMETRIC, ICE MACHINE RISER. WATER
 HAMMER ARRESTORS ARE REQUIRED AT EACH
 WASH MACHINE PER 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS.
 16) P-10 STORM WATER RISER DIAGRAM, THE
 HORIZONTAL PIPE SIZE IS NOT CORRECT
 WHERE 4"SD (2060 SF) & 4"SD (2160 SF)
 MAXIMUM 1600 SF FOR 4" PIPE @ 1/8" PER
 FOOT. SIZE ALL HORIZONTAL PIPE SECTIONS.
 17) SHT P-12 ALL PUMPS SHALL BE LISTED
 BY AN APPROVED TESTING AGENCY. SUBMIT
 MANUF. SPECS SHEETS. 303.4
 18) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION REQUIRED:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 SHOW VENTING IF DIRECT VENT.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS