Plan Review Notes
Plan Review Notes For Permit 03121642
Permit Number 03121642
Review Stop M
Sequence Number 1
Notes
Date Text
2004-02-20 00:00:00DENIED:
 1.PLAN SHEET AC-2, FIRE DAMPERS ON
 THE SUPPLY DUCT TO AHU-1 & EF-5 ARE
 INDICATED IN THE MIDDLE OF THE CORRIDOR
 AND NOT IN THE RATED WALL.PLEASE
 RELOCATE.
  
 2.PLAN SHEET AC-2, EXHAUST FROM THE
 DRYER RUNS TO A PLENUM BOX.PLEASE
 CLARIFY TERMINATION OF EXHAUST.
  
 3.DUCTS PENETRATING ONE FLOOR SHALL
 BE PROTECTED BY A FIRE DAMPER AT FLOOR
 PENETRATION.DUCTS PENETRATING MORE
 THAN ONE FLOOR SHALL BE PROTECTED BY A
 SHAFT ENCLOSURE PER 2001 FBC(M) 607.4.
  
 4.AC-3 DUCTS PENETRATING RATED WALLS
 WITHOUT FIRE DAMPERS SHALL COMPLY WITH
 2001 FBC(M) 607.1.3 #3 ITEMS 1 THROUGH
 4. SOME DUCTS ARE LESS THAN 5 FT BEFORE
 AN OPENING.PLEASE CLARIFY.
  
 5.PLAN SHEET AC-6, EXHAUST RISERS
 APPEAR TO TERMINATE BELOW THE ROOF,
 PLEASE CLARIFY.PROVIDE DETAIL OF
 CAP/FAN FOR ROOF TERMINATION.
  
 6.PLEASE INDICATE WHAT WILL BE STORED
 IN THE POOL/SPA EQUIPMENT ROOM.
 PROVIDE INFORMATION AND AMOUNTS OF ANY
 CHEMICALS THAT MAY BE STORED IN THIS
 AREA.
  
 7.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE GAS WATER HEATERS.
 PROVIDE DETAIL FOR THE VENTING OF
 WATER HEATERS.
  
 8.PLAN SHEET A-102 INDICATES FUTURE
 KITCHEN/RESTAURANT, NO INDICATION OF
 WHERE THE EXHAUST FOR THE HOOD MIGHT
 TERMINATE.PLEASE NOTE, TERMINATION
 FOR GREASE DUCT SHALL COMPLY WITH 2001
 FBC(M) 506.3.14.3.EXHAUST SHALL NOT
 TERMINATE WHERE PROTECTED OPENINGS ARE
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.