2004-02-20 00:00:00 | DENIED: |
| 1.PLAN SHEET AC-2, FIRE DAMPERS ON |
| THE SUPPLY DUCT TO AHU-1 & EF-5 ARE |
| INDICATED IN THE MIDDLE OF THE CORRIDOR |
| AND NOT IN THE RATED WALL.PLEASE |
| RELOCATE. |
| |
| 2.PLAN SHEET AC-2, EXHAUST FROM THE |
| DRYER RUNS TO A PLENUM BOX.PLEASE |
| CLARIFY TERMINATION OF EXHAUST. |
| |
| 3.DUCTS PENETRATING ONE FLOOR SHALL |
| BE PROTECTED BY A FIRE DAMPER AT FLOOR |
| PENETRATION.DUCTS PENETRATING MORE |
| THAN ONE FLOOR SHALL BE PROTECTED BY A |
| SHAFT ENCLOSURE PER 2001 FBC(M) 607.4. |
| |
| 4.AC-3 DUCTS PENETRATING RATED WALLS |
| WITHOUT FIRE DAMPERS SHALL COMPLY WITH |
| 2001 FBC(M) 607.1.3 #3 ITEMS 1 THROUGH |
| 4. SOME DUCTS ARE LESS THAN 5 FT BEFORE |
| AN OPENING.PLEASE CLARIFY. |
| |
| 5.PLAN SHEET AC-6, EXHAUST RISERS |
| APPEAR TO TERMINATE BELOW THE ROOF, |
| PLEASE CLARIFY.PROVIDE DETAIL OF |
| CAP/FAN FOR ROOF TERMINATION. |
| |
| 6.PLEASE INDICATE WHAT WILL BE STORED |
| IN THE POOL/SPA EQUIPMENT ROOM. |
| PROVIDE INFORMATION AND AMOUNTS OF ANY |
| CHEMICALS THAT MAY BE STORED IN THIS |
| AREA. |
| |
| 7.PLEASE PROVIDE COMBUSTION AIR |
| CALCULATIONS FOR THE GAS WATER HEATERS. |
| PROVIDE DETAIL FOR THE VENTING OF |
| WATER HEATERS. |
| |
| 8.PLAN SHEET A-102 INDICATES FUTURE |
| KITCHEN/RESTAURANT, NO INDICATION OF |
| WHERE THE EXHAUST FOR THE HOOD MIGHT |
| TERMINATE.PLEASE NOTE, TERMINATION |
| FOR GREASE DUCT SHALL COMPLY WITH 2001 |
| FBC(M) 506.3.14.3.EXHAUST SHALL NOT |
| TERMINATE WHERE PROTECTED OPENINGS ARE |
| REQUIRED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561) 805-6719. |