2004-01-22 00:00:00 | 1) TAMPER SWITCHES, CHAIN AND LOCK |
| ARE REQUIRED ON FIRE LINE BACKFLOW |
| DEVICE. |
| |
| 2) PROPOSED FIRE DEPARTMENT CONNECTION |
| SHALL BE BE WITHIN 150 FEET OF A |
| FIRE HYDRANT. |
| |
| 3) A KNOX-BOX WILL BE REQUIRED. |
| |
| 4) A TEMPORARY STANDPIPE WILL BE |
| REQUIRED WHEN THE BUILDING REACHES |
| THREE STORIES OR THIRTY FEET IN |
| HEIGHT. |
| |
| 5) STAIRS ARE TO BE KEPT UP WITH |
| CONSTRUCTION. |
| |
| 6) WILL THE PARALLEL PARKING SPACES |
| ON FERN STREET INTERFERE WITH THE |
| FIRE DEPARTMENT CONNECTION LOCATION. |
| |
| 7) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATION FOR WALLS AND CEILINGS. |
| |
| 8) PLEASE INDICATE ALL FIRE |
| EXTINGUISHER LOCATIONS. |
| |
| 9) BUILDING ADDRESS NOT SHOWN ON |
| ELEVATION DRAWING. A MINIMUM 6" HIGH |
| NUMBERS ARE REQUIRED. |
| |
| 10) PLEASE INDICATE PRESCRIPTIVE |
| CODE REQUIREMENTS FOR ALL HANDRAILS |
| AND GUARDRAILS. |
| |
| 11) EMERGENCY INSTRUCTIONS ARE REQUIRED |
| IN EACH GUESTROOM. |
| |
| 12) NO COMBUSTIBLES ARE ALLOWED IN |
| RETURN AIR PLENUMS. |
| |
| 13) SOME EXIT SIGNS APPEAR TO BE |
| MISSING FROM PAGE E-1. |
| |
| 14) EMERGENCY LIGHTS NEEDED IN BATHROOMS |
| ON FIRST FLOOR. |
| |
| 15) EMERGENCY LIGTING REQUIRED IN FIRE |
| PUMP ROOM. |
| |
| 16) SMOKE DETECTORS APPEAR TO BE |
| MISSING IN SEVERAL LOCALES ON PAGE E-3. |
| |
| 17) FUTURE RESTAURANT AREA IS TO BE |
| FIRE SPRINKLER PROTECTED PRIOR TO |
| HOTEL REQUESTING A C OF O. |
| |
| 18) SEPARATE PLANS AND PERMITS REQUIRED |
| FOR FIRE SPRINKLER AND FIRE ALARM |
| SYSTEM. |
| |
| 19) SHAFTS LARGE ENOUGH FOR PERSONS |
| TO FALL INTO SHALL BE MARKED SHAFTWAY. |
| |
| 20) PLEASE INDICATE ROOMS DESIGNATED |
| FOR THE HEARING IMPAIRED AND DESIGNATE |
| FIRE ALARM VISUAL DEVICES. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |