2004-02-11 00:00:00 | *************** UNSAT ************* |
| |
| 1)NOTE: PLEASE SEE 210.60A AND 210.52 |
| FOR RECEPT SPACING IN UNITS/ROOMS. |
| THERE ARE MANY MISSING FOR 2' OF WALL |
| SPACE AND W/IN 6' OF DOORWAYS. |
| |
| 2)NOTE: PLEASE PROVIDE NOTE ON PLANS |
| FOR REQUIRED BUSWAY/BUSDUCT CURBING PER |
| 368.8B(2) |
| |
| 3)NOTE: PLEASE CLARIFY USEAGE. PERMIT |
| APPLICATION AND PLANS CALL FOR A NEW |
| 5 STORY HOTEL. ELECTRICAL PLANS HAVE |
| EACH INDIVIDUAL UNIT ON A SEPARATE |
| ELECTRICAL METER FROM FPL. PLEASE |
| PROVIDE INFORMATION FROM FPL AND OR HOW |
| THIS FITS INTO BEING A HOTEL? IS BILLING |
| FOR ALL METERS GOING TO ONE OWNER? ARE |
| THESE "EXTENDED STAY" UNITS? ETC |
| PLEASE PROVIDE FPL'S CONFORMATION OF |
| THIS. |
| THIS IS ALSO PROVIDING A POINT IN THE |
| UDP TO RUN POWER TO OTHER LOCALS W/OUT |
| BEING METERED FROM FPL.PLEASE VERIFY |
| ALL OF THE ABOVE. |
| |
| 4)NOTE: PLEASE PROVIDE ALL INFORMATION |
| ON PLANS AND TITLE BLOCKS PER FAC |
| 61G1-16.004 FOR ARCH'S. THE ADDRESS |
| IS REQ'D ON PLANS/ TITLE BLOCK. |
| PLEASE ALSO SEE LICENSE INFORMATION FOR |
| ARCH'S FIRM IS MISSING AS REQ'D PER |
| ABOVE. PLEASE ALSO SEE FS 481.219 FOR |
| REQ'D CERTIFICATE OF AUTHORIZATIONFOR |
| |
| 5)NOTE: PLANS SHOW NEW POOL, HOWEVER |
| POOL IS REQ'D TO BE UNDER A SEAPARATE |
| PERMIT. |
| PLEASE PROVIDE NOTE ON PLANS IN FOR |
| TIMES OF PERMITTED SWIMMING. IF SWIMMING |
| IS GOING TO BE AFTER DUSK. A PHOTOMETRIC |
| STUDY WILL BE REQUIRED AND PLANS WILL |
| ALSO REQ'D TO BE STAMPED BY THE PALM |
| BEACH COUNTY HEALTH DEPT. |
| |
| 6)NOTE:PLEASE SEE PANEL "HA", SHOW CIR- |
| -CUIT FOR DRYER AT 5KW, HOWEVEROCP |
| IS SHWON AT 2P-20A? |
| |
| 7)NOTE: PLEASE SEE "DWELLING UNIT" |
| DEFINITION IN NEC AND OTHER CODES. |
| PLEASE SEE USAGE AND THE AMOUNT OF |
| LAUNDRY FIXTURES REQ'D. |
| PLEASE SEE PLUMB COMMENTS. |
| THIS QUESTION WILL COINCIDE WITH NOTE |
| #3 ABOVE. |
| |
| 8)NOTE: PLEASE "UDP", SHOWN AS BEING MLO |
| WITH TWO MAINS IN EQUIPMENT, HOWEVER |
| "UDP" IS SHOWN AS HAVING 42 SPACES?? |
| PLEASE SEE THIS IS NOT PERMITTED DUE TO |
| THE AMOUNT OF SPACES FOR A POSSIBLE |
| ADDITION OF 33 MORE MAINS? (1P BRKRS). |
| PLEASE SEE 230.71.A MCB MAY BE INSTALL |
| -ED? |
| |
| 9)NOTE: PLEASE SEE ALL PANEL SCHEDULES, |
| FEEDERS/ RISER DIAGRAM IS MISSING |
| EQUIPMENT GROUNDING CONDUCTORS PER |
| 250.110,250.24 ETC , SIZE PER 250.122 |
| |
| 10)NOTE: PLEASE PROVIDE COMPLETE FIXTURE |
| SCHEDULE. |
| |
| 11)NOTE: PLEASE SEE AREAS REQUIRED TO |
| MEET 700.16. |
| PLEASE ALSO SEE FIRE REVIEW COMMENTS |
| FOR EM/EXT LTS REQUIRED. SEE EM/EXT FIX- |
| -TURES SHOWN INDICATE HAVING AN EMERGEN- |
| -CY BALLAST,HOWEVER NO INDICATION OF |
| BATTERY BACK UP PER 700.12 |
| |
| 12)NOTE: PLEASE INDICATE/SHOW ALL HEIGHT |
| -S FOR ALL ELECTRICAL DEVICES PER |
| FHAR 24CFR 100.205. (FAIR HOUSING) |
| |
| 13)NOTE: PLEASE PROVIDE ALL INFORMATION |
| FOR FIRE PUMP. PLEASE ALSO PROVIDE |
| INFORMATION ON RISER DIAGRAM FOR FIRE |
| PUMP. PLEASE SEE 695.4B1 |
| PLEASE ALSO SEE 230.76, 230.79 FOR |
| DISCONNECTING MEANS. PLEASE ALSO NOTE |
| SIGNAGE FOR FIRE PUMP/LOCATION ETC IS |
| REQ'D TO BE NOTED ONPLANS.(SIGNAGE) |
| |
| 14)NOTE: PLEASE SEE RISER DIAGRAMS SHOWS |
| FUTURE CONDUITS FOR RESTARUANT, YET |
| ON THE RIGHT HAND SIDE OF E-7 , NOTE |
| MENTIONS A 3P-400A MCB? PLEASE CLARIFY |
| IF A MAIN IS GOING TO BE INSTALLED AT |
| THIS TIME. IF SO, PLEASE PROVIDE INFOR- |
| -MATION FOR DISC. IF NOT, PLEASE ADJUST. |
| |
| 15)NOTE: PLEASE SEE GUTTER SIZE SHOWN, |
| RISER APPEAR TO BE A MISPRINT FOR THE |
| SIZE OF 12"X12"X6",, SHOULD BE 6'? |
| |
| 16)NOTE: PLEASE SEE PANEL "HB", SHOWN |
| AS 22.5 A'S. (MISPRINT)? 225A'S. |
| "HB" HAS 200A OCP FEED. |
| |
| 17)NOTE: PLEASE NOTE ON PLANS ALL |
| ELECTRICAL WORK TO MEET 2002 NEC. |
| |
| 18)NOTE: PLEASE SEE LOAD CALCULATIONS |
| ON E-6, SHOWN AS 48 UNITS? PLEASE VERIFY |
| THE OTHER 8 MISSING UNITS? |
| 215.5 |
| |
| 19)NOTE: PLEASE SEE 215.3,230.42 ETC, |
| ALL CONTINUOUS LOADS ARE ALSO TO BE |
| SHOWN AT 125%, NOT JUST THE LARGEST |
| MOTOR LOAD. |
| |
| 20)NOTE: PLEASE SEE THAT ELEVATOR MAINS |
| ARE SHOWN AS ELEV 1,2 WHICH IS FINE. |
| HOWEVER, THEY ARE ALSO MAINS 5,6? |
| PLEASE ADJUST NOTES. |
| |
| 21)NOTE: PLEASE SEE SD LOCATIONS TO |
| MEETNFPA-72 8-1.4.1.6.2 |
| PLEASE SEE 8-1.4.2, SD'S REQUIRMENTS |
| W/IN 20'OF COOKING APPLIANCES. PLEASE |
| ALSO SEE 3' FROM BATH DOORS. PLEASE |
| SEE WHICH TYPE ARE PERMITTED. |
| |
| PLEASE SEE ONE SET OF PLANS HAVE MOST |
| ITEMS HIGHLIGHTED. PLEASE SEE, RAILING |
| AREA OF SECOND FLOOR MEZZ UNITS ARE |
| CONSIDERED WALL SPACE PER NEC, AND ARE |
| REQ'D TO MEET 210.52 ALSO. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |