Plan Review Notes
Plan Review Notes For Permit 03121565
Permit Number 03121565
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) PER RULING FROM THE FBPE A SIGNATURE
 IN REQUIRED BY ENGINEER ON SEAL. INIT-
 IALS ARE NOT ACCEPTABLE. 61G15-23.002(2)
 FS 471.
 2) BREAK ROOM SINK MAX HEIGHT IS 2'10"
 PER SECTION 11-4.24.2. SHOW CLEAR FLOOR
 SPACE PER 11-4.24.5. IF PARALLEL APPRO-
 ACH THE SINK SHALL BE CENTERED IN THE
 48" MEASURMENT.
  
 REVIEW BY KEN STEVENS