Plan Review Notes For Permit 03121563 |
Permit Number |
03121563 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-22 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | PRODUCT APPROVAL FOR WINDOWS, DOORS, | | MULLIONS, GLASS BLOCK, ROOF TILE AND | | STRUCTURAL CONNECTORS. | | 2-REVISE DETAIL E/4. 3" TAPCON DOESN'T | | PROVIDE THE 2" MIN. PENETRATION. | | 3-PROVIDE ENGINEERING CALCS FOR ANCHOR | | FASTENERS DIFFEENT THAN THOSE TESTED | | AND PUBLISHED BY USP TO COMPLY WITH | | SEC. 1609.4.3 FBC 2001 REGARDING THE | | STEEEL STRESS INCREASE. | | 4-REVISE DETAIL A/4. WHERE ARE TABLES 6 | | AND 8 TAKEN FROM? SEE FBC 2001 AND | | ASCE 7-98. | | 5-SHEET #7: A)REVISE DESIGN PRESSURES | | FOR EXTEIOR OPENINGS. SEE TABLES | | 1606.2B AND 1606.2E FBC 2001. | | B)DESIGN PRESSURES SHOWN ON THIS SHEET | | DON'T MATCH THOSE SHOWN ON SHEET 3. | | C)REVISE REAR PORCH FLOOR PLAN AND ROOF | | PLAN NOTES REGARDING WOOD BEAM,. SINCE | | IT WAS CHANGED TO CONCRETE BEAM. | | D)WINDOWS SHOWN ON EXTERIOR ELEVATION | | DON'T MATCH WINDOW SCHEDULE. REVISE. |
|