Plan Review Notes For Permit 03121541 |
Permit Number |
03121541 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-20 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) MORE INFORMATION REQUIRED. | | A. WHAT IS THE OCCUPANCY OF THE BLDG? | | B. IS THERE A DRINKING FOUNTAIN EXIST- | | ING? | | C. IS THE EXISTING SINK A SERVICE TYPE | | SINK? | | 2) PLEASE GIVE THE DIMENSIONS OF THE NEW | | ACCESSIBLE TOILET ROOM. 104.2.1 | | 3) INDICATE TYPE AND AMOUNT OF STORAGE. | | 4) SINK TRAP SHALL NOT BE UNDERGROUND ON | | PLUMBING RISER. SHOW TRAP ABOVE GROUND | | ON VENT RISER. MUST REFLECT INSTALLATION | | 5) WATER CLOSET SHALL NOT BE DOUBLE | | TRAPPED. NO TRAP UNDERGROUND FOR W/C. | | SECTION 1002.1 | | 6) SUBMIT A WATER RISER DIAGRAM PER SEC. | | 104.3.1.1 | | 7) SUBMIT DETAIL FOR ACCESSIBLE TOILET | | ROOM AND FIXTURES PER 11-4.16, 11-4.19, | | AND 11-4.22 AND ALL SUBSECTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|