Plan Review Notes
Plan Review Notes For Permit 03121541
Permit Number 03121541
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) MORE INFORMATION REQUIRED.
 A. WHAT IS THE OCCUPANCY OF THE BLDG?
 B. IS THERE A DRINKING FOUNTAIN EXIST-
 ING?
 C. IS THE EXISTING SINK A SERVICE TYPE
 SINK?
 2) PLEASE GIVE THE DIMENSIONS OF THE NEW
 ACCESSIBLE TOILET ROOM. 104.2.1
 3) INDICATE TYPE AND AMOUNT OF STORAGE.
 4) SINK TRAP SHALL NOT BE UNDERGROUND ON
 PLUMBING RISER. SHOW TRAP ABOVE GROUND
 ON VENT RISER. MUST REFLECT INSTALLATION
 5) WATER CLOSET SHALL NOT BE DOUBLE
 TRAPPED. NO TRAP UNDERGROUND FOR W/C.
 SECTION 1002.1
 6) SUBMIT A WATER RISER DIAGRAM PER SEC.
 104.3.1.1
 7) SUBMIT DETAIL FOR ACCESSIBLE TOILET
 ROOM AND FIXTURES PER 11-4.16, 11-4.19,
 AND 11-4.22 AND ALL SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved