Plan Review Notes
Plan Review Notes For Permit 03121541
Permit Number 03121541
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-26 00:00:00DENIED:
 1.PLEASE VERIFY ANY NEW OR EXISTING
 FIRE DAMPERS.
  
 2.PLEASE SEE THE ATTACHED SCHEDULE ON
 HEIGHT REQUIREMENTS FOR THE CONDENSING
 UNIT STANDS.
  
 3.SEE COMMENTS FROM MIKE CARSILLO FIRE
 DEPARTMENT, ON "STORAGE" AND OCCUPANT
 USE.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER NFPA 90A
 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.