Plan Review Notes For Permit 03121541 |
Permit Number |
03121541 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-26 00:00:00 | DENIED: | | 1.PLEASE VERIFY ANY NEW OR EXISTING | | FIRE DAMPERS. | | | | 2.PLEASE SEE THE ATTACHED SCHEDULE ON | | HEIGHT REQUIREMENTS FOR THE CONDENSING | | UNIT STANDS. | | | | 3.SEE COMMENTS FROM MIKE CARSILLO FIRE | | DEPARTMENT, ON "STORAGE" AND OCCUPANT | | USE. | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS PER NFPA 90A | | 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|