Plan Review Notes
Plan Review Notes For Permit 03121519
Permit Number 03121519
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE ASSEMBLY. F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES.
 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO INCLUDE ALL REQUIRED
 COMPONENTS ON LISTED ASSEMBLY. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC/01 REGARDING STEEL STRESS
 B)SPECIFY SIZES FOR USP RT CONNECTORS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER AS REQ'D BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHER IS USP EHUH
 28-3 TAKEN FROM?. UNABLE TO FIND ON
 USP 2003 CATALOGUE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)MISSING CONNECTOR FOR REAR PORCH
 GIRDER. SEC. 104.2.1.2 CITY AMENDMENTS
 C)CLARIFY CALCULATED DESIGN PRESSURES.
 WHY SAME PRESSURES FOR DIFFERENT SIZE
 AND LOCATION OF OPENINGS?. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)SHOW TYPE OF WINDOWS ON REAR ELEVATION
 SEE WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.