2004-01-06 00:00:00 | ************** UNSAT ***************** |
| |
| 1)NOTE: PLEASE LIST AND SHOW ALL MIN |
| CIRCUITING REQ'D ON PANEL SCHEDULE FOR |
| NEW WORK. 210.12/ 210.11C3, |
| |
| 2)NOTE: PLEASE CLARIFY IF BATH ROOM |
| DOORS ARE MISSING FROM BEDROOM #2 AND |
| FROM MASTER BEDROOM? |
| |
| 3)NOTE: PLEASE SEE FBC CHAPTER 34, FOR |
| ADDTIONS TO EXISTING BLDGS. PLEASE |
| SHOW EXISTING ELECTRICAL THAT MEETS |
| CODE OR THAT WILL BE REQ'D TO BE BROUGHT |
| UP TO CODE. |
| |
| 4)NOTE: PLEASE SEE NOTE ON RISER DIAGRAM |
| , MENTIONS,,,IF BRKR DOES NOT FIT, |
| PROVIDE DOUBLE LUG METER. PLEASE SEE |
| 230.72 FOR GROUPING OF MAINS ETC. |
| PLEASE ALSO VERIFY THIS INFOMATION AT |
| THIS TIME AND HAVE RISER DIAGRAM |
| REFLECT CODE COMPLIANCE AND WHICH PATH |
| WILL BE TAKEN. |
| PLEASE ALSO SEE THAT RISER DIAGRAM SHOWS |
| FPL SEC'S GOING INTO MAIN PANEL AND |
| THEN OUT TO METER AND BACK TO MAIN |
| PANEL. PLEASE SEE NEC. LINE AND LOAD IN |
| PANEL IS NOT PERMITTED. |
| |
| 5)NOTE: PLEASE SHOW LOCATION OF NEW |
| PANEL. |
| |
| 6)NOTE: PLEASE ALSO SHOW LOCATION OF |
| NEW AHU. PANEL SCHEDUL SHOWS NEW CU, BUT |
| NOT AHU???? |
| |
| 7)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| AND PANELS. 100A PANEL IS SHOWN AS MLO, |
| AND PANEL SHOWS 100A MCB. |
| |
| 8)NOTE: PLEASE SEE LOAD CALCULATIONS, |
| SHOWS , SHOWS ADDITION BEING 1070 SQ FT |
| AND YET TOTAL ON LOAD CALCS SHOWS SQ FT |
| AT 1100 TOTAL?????? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION AND |
| PLEASE CORRELATE TO 2002 NEC. IF THERE |
| ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |