Plan Review Notes
Plan Review Notes For Permit 03121505
Permit Number 03121505
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-06 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE LIST AND SHOW ALL MIN
 CIRCUITING REQ'D ON PANEL SCHEDULE FOR
 NEW WORK. 210.12/ 210.11C3,
  
 2)NOTE: PLEASE CLARIFY IF BATH ROOM
 DOORS ARE MISSING FROM BEDROOM #2 AND
 FROM MASTER BEDROOM?
  
 3)NOTE: PLEASE SEE FBC CHAPTER 34, FOR
 ADDTIONS TO EXISTING BLDGS. PLEASE
 SHOW EXISTING ELECTRICAL THAT MEETS
 CODE OR THAT WILL BE REQ'D TO BE BROUGHT
 UP TO CODE.
  
 4)NOTE: PLEASE SEE NOTE ON RISER DIAGRAM
 , MENTIONS,,,IF BRKR DOES NOT FIT,
 PROVIDE DOUBLE LUG METER. PLEASE SEE
 230.72 FOR GROUPING OF MAINS ETC.
 PLEASE ALSO VERIFY THIS INFOMATION AT
 THIS TIME AND HAVE RISER DIAGRAM
 REFLECT CODE COMPLIANCE AND WHICH PATH
 WILL BE TAKEN.
 PLEASE ALSO SEE THAT RISER DIAGRAM SHOWS
 FPL SEC'S GOING INTO MAIN PANEL AND
 THEN OUT TO METER AND BACK TO MAIN
 PANEL. PLEASE SEE NEC. LINE AND LOAD IN
 PANEL IS NOT PERMITTED.
  
 5)NOTE: PLEASE SHOW LOCATION OF NEW
 PANEL.
  
 6)NOTE: PLEASE ALSO SHOW LOCATION OF
 NEW AHU. PANEL SCHEDUL SHOWS NEW CU, BUT
 NOT AHU????
  
 7)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. 100A PANEL IS SHOWN AS MLO,
 AND PANEL SHOWS 100A MCB.
  
 8)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS , SHOWS ADDITION BEING 1070 SQ FT
 AND YET TOTAL ON LOAD CALCS SHOWS SQ FT
 AT 1100 TOTAL??????
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 PLEASE CORRELATE TO 2002 NEC. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]