2004-01-20 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR ALL WINDOW/DOOR |
| TYPES, GLASS BLOCK, MULLIONS, ROOF |
| TILE AND STRUCTURAL CONNECTORS. |
| 2-REVISE DETAIL E/4. FASTENER SPECIFIED |
| DOESN'T PROVIDE 2" MIN. EMBEDMENT. SEC |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 3-PROVIDE ENGINEERING CALCS FOR NUMBER |
| OF FASTENERS SPECIFIED FOR TRUSS |
| ANCHORS SINCE THEY DIFFER FROM THOSE |
| TESTED AND PUBLISHED BY USP TO COMPLY |
| WITH SEC. 1609.4.3 FBC 2001 REGARDING |
| THE STEEL STRESS.SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 4-REVISE DETAIL A/4. WHERE ARE TABLES 6 |
| AND 8 TAKEN FROM?. WE USE ASC7 7-98 OR |
| FBC 2001. |
| 5-SHEET A-7: A)REVISE DESIGN PRESSURES @ |
| EXTERIOR OPENINGS. SEE TABLES 1606.2B |
| AND 1606.2E FBC 2001. |
| B)DESIGN PRESSURES SHOWN ON SHEET 7 AND |
| SHEET 3 DON'T MATCH. REVISE AS REQ'D. |
| C)REVISE REAR PORCH FLOOR PLAN AND ROOF |
| FRAMING PLAN. CHANGE NOTES RELATED TO |
| WOOD BM. SINCE IT WAS CHANGED TO CONC. |
| BEAM. SEC. 104.2.1.2 CITY AMENDMENTS. |
| D)WINDOWS SHOWN ON ELEVATION DON'T MATCH |
| THOSE SPECIFIED ON WINDOW SCHEDULE. |