Plan Review Notes
Plan Review Notes For Permit 03121504
Permit Number 03121504
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW.
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE ASEMBLY. F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHTECT TO HAVE ALL HIS INFORMATION
 AND PROVIDE ALL INFORMATION AS REQ'D
 BY CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING DWGS FOR PUBLIC RECORDS.
 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL IDENTIFYING ALL REQ'D
 COMPONENTS ON SUCH ASSEMBLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZES FOR USP STRAP RT.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER AS REQ'D BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHERE IS USP EHUH
 28-3 CONNECTOR TAKEN FROM?. UNABLE TO
 FIND ON USP 2003 CATALOGUE.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR FOR REAR PORCH
 GIRDER TRUSS.SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)CLARIFY CALCULATED DESIGN PRESSURES.
 WHY THE SAME PRESSURES FOR DIFFERENT
 SIZE AND LOCATION OF OPENING?.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)REAR ELEVATION DOESN'T REFLECT TYPE OF
 WINDOWS SPECIFIED ON WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.