Plan Review Notes For Permit 03121499 |
Permit Number |
03121499 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-22 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | PRODUCT APPROVAL FOR ALL DOORS,WINDOWS | | GLASS BLOCK, ROOF TILE, MULLIONS AND | | STRUCTURAL CONNECTORS. | | 2-REVISE DETAIL E/4. FASTENER SPECIFIED | | DOESN'T PROVIDE 2" MIN. EMBEDMENT. | | 3-PROVIDE ENGINEERING CALCULATIONS FOR | | TRUSS ANCHORS WITH DIFFERENT FASTENERS | | AS TESTED AND PUBLISHED BY USP TO | | COMPLY WITH SEC. 1609.4.3 FBC 2001. | | 4-REVISE DETAIL A/4. WHERE ARE TABLES 6 | | AND 8 TAKEN FROM?. SEE FBC 2001 OR | | ASCE 7-98. | | 5-SHEET #7: A)REVISE DESIGN PRESSURES AT | | EXTERIOR OPENINGS. SEE TABLES 1606.2B | | AND 1606.2E FBC 2001. | | B)DESIGN PRESSURES SHOWN ON THIS SHEET | | DON'T MATCH THOSE SHOWN ON SHEET 3. | | C)REVISE REAR PORCH FLOOR PLAN AND ROOF | | PLAN RELATING TO WOOD GIRDER, SINCE IT | | WAS CHANGED TO CONCRETE BEAM. | | D)WINDOWS SHOWN ON EXTERIOR ELEVATION | | DON'T MATCH WINDOW SCHEDULE. |
|