Plan Review Notes
Plan Review Notes For Permit 03121499
Permit Number 03121499
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-13 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOWS
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE. F)SLIDING GLASS DOORS. G)WINDOW
 MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO PROVIDE ALL REQUIREMENTS
 OF CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING DWGS FOR PUBLIC RECORDS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 REQUIRED ON SUCH LISTING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL E/4 & NOTES ON DWG
 #2 DON'T MATCH. CHECK FASTENER SIZE.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZES FOR USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)WHERE IS USP EHUH 28-3
 TAKEN FROM?. UNABLE TO FIND IN 2003
 USP CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR AT GIRDER TRUSS
 LOCATED AT REAR PORCH. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)WHY DESIGN PRESSURES ARE THE SAME FOR
 OPENINGS WITH DIFFERENT SIZE/LOCATION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.