Plan Review Notes
Plan Review Notes For Permit 03121490
Permit Number 03121490
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE FLORIDA/SITE SPECIFIC PRODUCT
 APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW. NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE (APPROVAL IS PENDING).
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
 H)TRUSS CONNECTORS.
  
 3-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES.
 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO INCLUDE ALL REQUIRED
 COMPONENTS OF SUCH ASSEMBLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER. SEC.104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001.
 B)SPECIFY SIZE OF USP RT ANCHOR TO BE
 USED. SEC. 104.2.1.2 CITY AMENDMENTS.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER AS REQ'D BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHERE IS USP
 EHUH 28-3 TAKEN FROM?. UNABLE TO FIND
 IN THE USP 2003 CATALOGUE.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)MISSING CONNECTOR FOR REAR PORH GIRDER
 TRUSS. SEC. 104.2.1.2 CITY AMENDMENTS.
 C)CLARIFY CALCULATED DESIGN PRESSURES.
 WHY SAME FOR DIFFERENT OPENING SIZE &
 LOCATION. SEC.104.2.1.2 CITY AMENDMENT
 D)SHOW TYPE OF WINDOW ON REAR ELEVATION.
 SEE WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.