2004-01-27 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR ALL DOOR & WINDOW |
| TYPES, GLASS BLOCK, ROOF TILE AND |
| STRUCTURAL CONNECTORS. |
| 2-DETAIL E/4 AND RESIDENTIAL NOTES ON |
| DRAWING #2 DON'T MATCH. REVISE AS |
| REQUIRED. |
| 3-CLARIFY/REVISE TRUSS ANCHOR SCHEDULE. |
| CHECK FOR TYPOS FOR CLARIFICATION OF |
| ANCHOR SPECS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 4-TYPICAL WALL SECTION DETAIL A/4. WHERE |
| ARE TABLES 6 AND 8 SHOWN FOR ROOF TILE |
| FASTENERS TAKEN FROM?. SEE SECTION |
| 1606.3.2 FBC 2001. |
| 5-SHEET #7: A)WINDOWS SHOWN ON REAR |
| ELEVATION DON'T MATCH THOSE SPECIFIED |
| ON WINDOW SCHEDULE. |
| B)REVISE ALL NOTES SHOWN ON FLOOR PLAN & |
| ROOF FRAMING PLAN. WOOD GIRDER WAS |
| CHANGED TO CONCRETE BEAM. SPECIFY |
| CORRECT ANCHOR AND DELETE NOTES THAT |
| ARE NO APPROPRIATE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| 6-SHEET #3: CLARIFY NOTE THAT READS: |
| "UPLIFT FOR EACH TRUSS ARE MORE THAN |
| THE MAXIMUM VALUE SHOWN FOR THE |
| CONNECTOR SELECTED".SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |