Plan Review Notes
Plan Review Notes For Permit 03121489
Permit Number 03121489
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: A)SLIDER WINDOW.
 B)GLASS BLOCK. C)ROOF TILE. D)SINGLE
 HUNG WINDOWS. E)ENTRY DOOR WITH SIDE-
 LITE ASSEMBLY. F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS. H)TRUSS CONNECTORS.
 3-ARCHITECT TO HAVE ALL HIS INFORMATION
 AND REQUIREMENTS OF CHAPTER 481 FL.
 4- 1HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO INCLUDE ALL REQUIRED
 COMPONENTS ON LISTED ASSEMBLY.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 REVISE AS REQUIRED.
 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARD'G THE STEEL STRESS
 B)SPECIFY SIZES FOR USP RT CONNECTORS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 FASTENER AS REQ'D BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #7: A)CLARIFY WHERE IS USP EHUH
 28-3 CONNECTOR TAKEN FROM?. UNABLE TO
 FIND ON USP 2003 CATALOGUE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)MISSING ONE CONNECTOR FOR REAR PORCH
 GIRDER TRUSS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 C)CLARIFY WHY THE DESIGN PRESSURES ARE
 THE SAME FOR DIFFERENT OPENING SIZE &
 LOCATION. SEC. 104.2.1.2 CITY AMENDM.
 D)WINDOWS SHOWN ON REAR ELEVATION DON'T
 MATCH WINDOW SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.