Plan Review Notes For Permit 03121484 |
Permit Number |
03121484 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-ARCHITECT TO PROVIDE ALL DRAWINGS WITH | | INFORMATION AS REQ'D BY CHAPTER 481 FL | | STATUTES. SOME DWGS MISSING THIS INFO. | | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | PRODUCT APPROVAL FOR WINDOWS, DOORS, | | GLASS BLOCK, ROOF TILE, MULLIONS AND | | STRUCTURAL CONNECTORS. | | 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 | | DON'T MATCH. CHECK FASTENER SIZE. | | 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS | | FOR TYPE/NUMBER OF FASTENERS OTHER | | THAN THOSE TESTED AND PUBLISHED BY USP | | TO COMPLY WITH SEC. 1609.4.3 FBC 2001. | | 5-DESIGNER OF RECORD TO SPECIFY ROOF | | TILE FASTENERS. SEC. 104.2.1.1 CITY | | AMENDMENTS TO FBC 2001. | | 6-REVISE WINDOW BUCK DETAIL. SEE SECTION | | 1707.4.4.2 FBC 2001 FOR PROPER BUCK | | INSTALLATION. | | 7-SHEET #3: A)REVISE DESIGN PRESSURES. | | SEE TABLES 1606.2B & 1606.2E FBC 2001 | | FOR PRESSURES ACCORDING TO SIZE AND | | LOCATION. | | B)PROVIDE ENGINEERING CALCS FOR SIMPSON | | EG7 FASTENERS, SINCE THEY DIFFER FROM | | THOSE TESTED AND PUBLISHED BY USP TO | | COMPLY WITH SEC. 1609.4.3 FBC 2001. |
|