2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES
 WHEN SUBMITTING DRAWINGS FOR PUBLIC
 RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: ALL DOORS AND
 WINDOWS, ROOF TILE & TRUSS CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 LISTED ON THE ASSEMBLY. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK SIZE OF FASTENER.
 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF
 USP RT CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E ACCORDING TO SIZE & LOCATION.
 PROVIDE CALCULATIONS FOR DESIGN
 PRESSURES OTHER THAN THOSE PUBLISHED
 ON ABOVE TABLES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)SIMPSON EG7 CONNECTOR HAS DIFFERENT
 FASTENERS THAN THOSE PUBLISHED.PROVIDE
 ENGINEERING CALCS SHOWING COMPLIANCE
 WITH SEC. 1609.4.3 FBC 2001 WHICH DOES
 NOT ALLOW THE STEEL STRESS TO BE
 INCREASED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.