Plan Review Notes For Permit 03121481 |
Permit Number |
03121481 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-02-04 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-SOME DRAWINGS ARE MISSING INFORMATION | | REQUIRED BY ARCHITECT TO BE INCLUDED | | AS REQ'D BY CHAPTER 481 FL. STATUTES. | | 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC | | PRODUCT APPROVAL UNDER A SEPARATE | | PERMIT FOR ALL DOORS AND WINDOWS TO BE | | USED, GLASS BLOCK, ROOF TILE MULLIONS | | AND ALL STRUCTURAL CONNECTORS. | | 3-DETAIL E/4 AND RESIDENTIAL NOTES ON | | DWG #2 DON'T MATCH. REVISE AS REQUIRED | | 4-REVISE WINDOW BUCK DETAIL. SEE SECTION | | 1707.4.4.2 FBC 2001. | | 5-DWG #2: A)CLARIFY/REVISE TRUSS ANCHOR | | SCHEDULE. SEC. 104.2.1.2 CITY AMENDM. | | B)PROVIDE ENGINEER CALCS AND DETAILS AS | | SPECIFIED ON NOTE BELOW TRUSS ANCHOR | | SCHEDULE. | | 6-SPECIFY ROOF TILE FASTENERS. SECTION | | 104.2.1.1. CITY AMENDMENTS TO FBC 2001 | | 7-PROVIDE REVISED FRAMING AT REAR PORCH. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | 8-CLARIFY NOTE ONSHEET 3A REGARDING | | MAXIMUM UPLIFT VALUES & CONNECTORS. |
|