2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS/WINDOWS
 TYPE, ROOF TILE, GLASS BLOCK AND ALL
 STRUCTURAL COMPONENTS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 SPECIFIED ON SUCH ASEMBLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH CHECK FASTENER SIZE.
 6-TRUSS ANCHOR SCHEDULE: A)CONNECTORS TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001 FOR
 STEEL STRESS. REVISE FASTENER TYPE AND
 NUMBER AS SHOWN ON REVISED CATALOGUE.
 PROVIDE ENGINEERING CALCS FOR VALUES
 OTHER THAN THOSE PUBLISHED.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E ACCORDING TO SIZE & LOCATION.
 PROVIDE CALCS FOR DESIGN PRESSURES
 THAT SIGNIFICANTLY DIFFER FROM ABOVE
 TABLES. SEC. 104.2.1.2 CITY AMENDMENTS
 10-SIMPSON EG7 CONNECTOR SPECIFIED ON
 ROOF FRAMING PLAN SHOW DIFFERENT
 FASTENERS THAN SHOWN ON CATALOGUE.
 PROVIDE CALCS SHOWING COMPLIANCE WITH
 SEC. 1609.4.3 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.