2004-01-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-ARCHITECT TO COMPLY WITH ALL REQUIRE- |
| MENTS OF CHAPTER 481 FLORIDA STATUTES. |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR ALL DOORS/WINDOWS |
| TYPE, ROOF TILE, GLASS BLOCK AND ALL |
| STRUCTURAL COMPONENTS. |
| 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| FIRE RATED GLASS BLOCK ASSEMBLY AND |
| REVISE DETAIL TO SHOW ALL COMPONENTS |
| SPECIFIED ON SUCH ASEMBLY. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH CHECK FASTENER SIZE. |
| 6-TRUSS ANCHOR SCHEDULE: A)CONNECTORS TO |
| COMPLY WITH SEC. 1609.4.3 FBC 2001 FOR |
| STEEL STRESS. REVISE FASTENER TYPE AND |
| NUMBER AS SHOWN ON REVISED CATALOGUE. |
| PROVIDE ENGINEERING CALCS FOR VALUES |
| OTHER THAN THOSE PUBLISHED.SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)SPECIFY SIZE OF USP RT STRAPS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENER. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 9-REVISE DESIGN PRESSURES FOR EXTERIOR |
| OPENINGS. SEE TABLES 1606.2B AND |
| 1606.2E ACCORDING TO SIZE & LOCATION. |
| PROVIDE CALCS FOR DESIGN PRESSURES |
| THAT SIGNIFICANTLY DIFFER FROM ABOVE |
| TABLES. SEC. 104.2.1.2 CITY AMENDMENTS |
| 10-SIMPSON EG7 CONNECTOR SPECIFIED ON |
| ROOF FRAMING PLAN SHOW DIFFERENT |
| FASTENERS THAN SHOWN ON CATALOGUE. |
| PROVIDE CALCS SHOWING COMPLIANCE WITH |
| SEC. 1609.4.3 FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |